DRAFT, needs technical review. Not for publication. The title is our own wording, not the official Paris MoU text.

PSC deficiency code 04102: Emergency fire pump and sea suction arrangements

Category Emergency systems (SOLAS II-2)
Related certificate Cargo Ship Safety Equipment
Main references SOLAS II-2/10.2.1.3 and FSS Code
Typical action codes 17 (rectify before departure), 30 (detainable) if serious
Commonly detainable? Can be, depending on severity (no statistics claimed)

What PSC officers look for

  • Emergency fire pump fails to start or deliver pressure
  • Suction valve frozen or sea chest blocked
  • Fuel or power supply to pump inadequate
  • Emergency switch inaccessible or unmarked
  • No recent test with fire main isolated

Typical root causes

  • Infrequent testing of emergency pump alone
  • Sea chest fouling not addressed in underwater work
  • Battery or starter motor defects
  • Assumption that main fire pump test covers emergency unit

Corrective action (example)

Restore pump operation; clean suction; repair starter and fuel system; conduct standalone load test and record.

Preventive action (example)

Schedule monthly emergency pump test distinct from main pump; track sea chest maintenance.

Evidence to attach for close-out

  • Test log with pressure and duration
  • Work order for repairs
  • Photos of valve positions
  • Spare parts invoice if used

Related

  • Codes: 07113, 04103, 02108
  • SIRE 2.0: Chapter 5 (fire safety) (chapter reference only)

Generate a close-out report for this finding · Download the CAP template


Official code list: Paris MoU, List of Deficiency Codes (1 July 2026). Action codes: Paris MoU, Inspection outcome. Reviewed by: _pending_ · Review date: _pending_ This page is general guidance, not legal, flag or class advice. Always follow the PSC officer's instructions and your flag and class requirements.

Next steps

Generate a close-out report for this finding

Report an error on this page